A Multi-Phase Charge Program, typical: Deep-Discharge Recovery is automatically initiated by a series of controlled pulse trains, to be followed by a Soft-Charge-, a Constant Current- and a Constant Voltage Phase. The charge routine now transfers to the Float Charge Phase if the charge current has dropped to a pre-set, lower current threshold or if a given time limit has been reached, whichever is first. Float Charging can be skipped and replaced by Auto-Recharge instead, triggered by a set number of days elapsed or a given voltage drop across the battery terminals.
Custom-Tailored Charge Programs: Should the pre-set Charge Programs for Gel-, Wet-, AGM- and Ca-Batteries, or values for the Power Supply Mode, not meet the user's particular needs, MEC will customize the programs and write it to the JOE's controller, via the integrated IR-Data Port.